EPA 608 guide
Recovery and leak rules: the numbers the exam tests
Most 608 marks are won or lost on numbers. These are the ones that come up again and again — keep them straight and you have banked a large share of both Core and the type sections before you answer anything conceptual.
Small appliances — the 80/90 rule
Under 40 CFR 82.156, recovery from small appliances must reach 90% efficiency when the appliance's compressor is functioning, and 80% when it is not. Older study banks still test a legacy threshold based on charge weight, so know both framings and read the question carefully.
Larger systems — evacuation levels
Larger equipment is judged by how deep a vacuum you pull rather than a percentage recovered. High- and medium-pressure equipment under 200 lb has an evacuation target of 0 psig, and low-pressure systems use a much deeper target measured in millimetres of mercury. Your equipment class and the system's charge determine which applies.
Cylinder and handling rules
- Never fill a recovery cylinder above its rated capacity — use the 80% rule of thumb for liquid refrigerants unless the cylinder marking says otherwise
- Cylinders must be DOT-approved, labelled and never over-pressurised or heated with an open flame
- Recovered refrigerant must not be vented; it is either recycled, reclaimed, or destroyed by an approved facility
- Refrigerant sold to technicians must come from an EPA-certified recovery/recycling source
Leak rules in practice
Leak repair obligations depend on appliance class, charge size and the refrigerant's global-warming potential. The exam tests the thresholds and the record-keeping duty; the day job tests whether you can find the leak before the third visit. Learn the rule categories rather than memorising a single number — the questions change the appliance class on purpose.
Frequently asked
- What is the 80/90 rule?
- Recovery from a small appliance must reach 90% efficiency with the compressor running, 80% with it not running. Larger systems use evacuation vacuum levels instead.
- Can recovered refrigerant be reused?
- Recovered refrigerant can be recycled on site and reused in equipment owned by the same owner under the recovery rules; reclaimed refrigerant for other systems must meet the reclamation standard and come through an approved process.
Drill these numbers with the free practice exam →
Every question explains why the wrong answer is wrong.