Recovery and leak rules: the numbers the exam tests

Most 608 marks are won or lost on numbers. These are the ones that come up again and again — keep them straight and you have banked a large share of both Core and the type sections before you answer anything conceptual.

Small appliances — the 80/90 rule

Under 40 CFR 82.156, recovery from small appliances must reach 90% efficiency when the appliance's compressor is functioning, and 80% when it is not. Older study banks still test a legacy threshold based on charge weight, so know both framings and read the question carefully.

Larger systems — evacuation levels

Larger equipment is judged by how deep a vacuum you pull rather than a percentage recovered. High- and medium-pressure equipment under 200 lb has an evacuation target of 0 psig, and low-pressure systems use a much deeper target measured in millimetres of mercury. Your equipment class and the system's charge determine which applies.

Cylinder and handling rules

  • Never fill a recovery cylinder above its rated capacity — use the 80% rule of thumb for liquid refrigerants unless the cylinder marking says otherwise
  • Cylinders must be DOT-approved, labelled and never over-pressurised or heated with an open flame
  • Recovered refrigerant must not be vented; it is either recycled, reclaimed, or destroyed by an approved facility
  • Refrigerant sold to technicians must come from an EPA-certified recovery/recycling source

Leak rules in practice

Leak repair obligations depend on appliance class, charge size and the refrigerant's global-warming potential. The exam tests the thresholds and the record-keeping duty; the day job tests whether you can find the leak before the third visit. Learn the rule categories rather than memorising a single number — the questions change the appliance class on purpose.

Frequently asked

What is the 80/90 rule?
Recovery from a small appliance must reach 90% efficiency with the compressor running, 80% with it not running. Larger systems use evacuation vacuum levels instead.
Can recovered refrigerant be reused?
Recovered refrigerant can be recycled on site and reused in equipment owned by the same owner under the recovery rules; reclaimed refrigerant for other systems must meet the reclamation standard and come through an approved process.

Drill these numbers with the free practice exam →

Every question explains why the wrong answer is wrong.